ICP · Heat pump troubleshooting
Comfort Alert module basics
What is going on
The Comfort Alert module on the ICP N4H3 R-410A split heat pump (manual 428 01 5103 02) has three lights, and reading them correctly saves a lot of guessing. These codes apply only to units that were factory fitted with the Comfort Alert module. Confirm the module is present before relying on any of this, and treat the electrical checks as work for a qualified technician.
Likely causes
- Green POWER means the module is powered
- Red TRIP means there is a Y1 call but the compressor is off
- Yellow ALERT flashes a code: a number of flashes, a pause, then it repeats
Check in this order
- The module is powered from R and C (24 VAC) and watches the compressor leads and Y, so confirm 24 VAC at those terminals first.
- Reset an ALERT code by removing 24 VAC from the module.
- The last ALERT code shows for 1 minute after the module powers on, so count the flashes during that window.
- TRIP and ALERT flashing together means control voltage is too low; check the transformer and low voltage wiring.
- Match the flash count to the module's code table before replacing any component
Applies to: ICP N4H3 R-410A split heat pump (manual 428 01 5103 02); Comfort Alert codes apply only to units factory-fitted with the Comfort Alert module
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ICP N4H3 Installation Instructions 428 01 5103 02, Troubleshooting / Figure 17-18, p.19-20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.