Daikin · General troubleshooting
Wiring the thermostat to the translation adaptor
What is going on
Wire the thermostat to the adaptor with the correct gauge and length, and verify voltage at each stage.
Likely causes
- Wiring run too long
- Wrong wire gauge or conductor count
- Power wires reversed
- Incorrect wiring
Check in this order
- Use four-conductor 18 AWG field wire, no longer than 125 ft.
- Check voltage before wiring about 0.6 VDC between Data 1 and 2, and 24 VDC between R and C.
- Wire R, C, Data Line 1 and Data Line 2, plus 24 V power and 24 V common, as shown.
- Check voltage again after wiring.
- If the PWR LED flashes green, the power wires are reversed; correct them.
Applies to: Daikin One+ Smart Thermostat
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin One+ installation & commissioning (S21), p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.