Replace the dust collection filter and reset the alert
What is going on
Filter replacement lamp lit means about 1 month left. Lamp blinking means replace now.
Likely causes
- Filter replacement lamp blinking
Check in this order
- Stop operation, unplug the unit, then remove the water tank, humidifying tray and filter fixing unit.
- Remove the carbon filter by holding its side.
- Lift the tag on the dust collection filter and pull it out from the bottom.
- Insert the new filter with the tag and marking to the front and the arrow pointing up. Hold the filter down if it is hard to fit.
- Refit the carbon filter, filter fixing unit, humidifying tray and water tank.
- Press and hold the reset button for about 2 seconds. Two short beeps sound and the filter replacement lamp turns off.
- Do not vacuum the dust collection filter and do not wash it with water.
Applies to: Dust collection filter
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin MCKB70YSAU installation & operation manual, p. 26, 31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.