Remove and refit the humidifying tray and humidifying filter unit
What is going on
Needed for cleaning the tray and filter. The water tank must come out first.
Check in this order
- Stop operation, unplug the unit and remove the water tank.
- Pull the humidifying tray out slowly, lifting slightly, and hold the outer frame of the filter unit. Carry it by the bottom.
- To refit, fit the axle into the groove in the tray, then push the tray all the way in.
- Do not twist the humidifying filter unit once fitted, or a malfunction may result.
- Reinstall the water tank.
Applies to: Humidifying tray and humidifying filter unit
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin MCKB70YSAU installation & operation manual, p. 27-28. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.