Installing the heater accessory on the ventilator

Daikin One Powered Ventilator

What is going on

Mounting and wiring the heater to the ventilator cabinet. Disconnect power before starting.

Check in this order

  1. Switch off the main disconnect and lock or tag it.
  2. Remove the four screws holding the outlet duct collar and gasket on the ventilator, and set them aside.
  3. Fit the duct collar and gasket onto the heater end panel using those screws.
  4. Remove the two screws holding the ventilator control compartment cover and set them aside.
  5. Punch out the electrical knockout on the ventilator front with a straight-blade screwdriver.
  6. Remove and discard the foam insert behind the knockout.
  7. Fit the plastic bushing, run the heater harness through it and the knockout, and connect it to the 3-pin connector on the LCD controller.
  8. Secure the heater to the ventilator with the six screws: two per side and two on the bottom.
  9. Refit the control compartment cover with its two screws.

Applies to: DQ-P-70-AH-H heater with Daikin One Powered Ventilator

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: IO-DPVH installation and operation manual, p. 3. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.