Daikin · General troubleshooting

Install DQ-P-MDV motorized damper on DQ-P-16-100 ventilator

Daikin One Powered Ventilator

What is going on

Mount the motorized damper on the ventilator outlet side, wire it through a 24VAC transformer and harness, then test. Power must be off at the service panel during work.

Check in this order

  1. Switch power off at the service panel before starting.
  2. Remove the knock-out on the front of the DQ-P-16-100 ventilator with a straight blade screwdriver.
  3. Fit the supplied plastic bushing into the knock-out hole to protect the wires.
  4. Open the ventilator control compartment cover and unplug the 3-pin Molex cable from the 3-pin connector near the bottom of the compartment.
  5. Connect the new wire harness between the 3-pin connector and the original 3-pin cable.
  6. Attach the damper to the outlet (discharge) side of the ventilator using a 6 inch section of rigid duct. Seal with suitable rated tape and secure with screws or clamps. Repeat for any inline ducting after the damper.
  7. If the receptacle will face downward, move the electrical enclosure: remove the side plate screws, push the receptacle out of the enclosure, snap it into the side plate opening, and reinstall the side plate in the new opening.
  8. Plug the 24VAC transformer into the receptacle on the electrical enclosure so it does not hang straight down.
  9. Run the transformer lead wires to the damper and connect them to the pre-installed ends on the transformer.
  10. Feed the 2-pin connector from the harness through the bushing and connect it to the 2-pin receptacle inside the enclosure.
  11. Reinstall the control compartment cover. Tuck wires into the enclosure and mount the enclosure to the ventilator cabinet with the two supplied screws.
  12. Restore power and test operation.

Applies to: DQ-P-MDV with DQ-P-16-100 Powered Ventilator

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin IO-DPVMD motorized damper installation manual, p. 2-3. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.