General installation steps for the air cleaner
What is going on
Install the cabinet in the return duct close to the blower compartment, sealing all joints.
Check in this order
- Turn off the system fan and the electrical disconnect before starting work.
- Remove the existing equipment filter and thoroughly clean the blower compartment.
- Leave enough room in front of the cabinet to pull and replace the filter.
- Use a gradual transition if the duct does not match the opening. Keep it to about 20 degrees per side, or about 4 in per running foot. Do not shrink the ductwork.
- Add field turning vanes if the cabinet is next to an elbow.
- Remove the door, holding the outer panel with both hands, then remove the MERV 15 and RTC filters.
- Attach the cabinet to the furnace and filter riser, air handler or plenum with the ten self-tapping hex screws provided. Follow the airflow direction marked on the cabinet.
- Seal all joints and seams with aluminum tape or mastic.
- Reinstall the filters in the correct flow direction and remove the plastic bag from the RTC before installing it. Reinstall the door and check that it seats properly.
- If needed, slide the Daikin badge up, rotate it to the correct orientation and reinstall it.
Applies to: DV1-15 series air cleaners
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin One Premium Air Cleaner installation & operation manual, p. 3. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.