Daikin · General troubleshooting

Cleaning the sensor probe

Daikin One

What is going on

Dirt inside the two air passageways of the sensor probe can make the particulate readings inaccurate. Only a qualified electrician or HVAC technician should do this. If you are not qualified, contact the HVAC dealer.

Likely causes

  • Particulate buildup on the internal surfaces of the sensor probe passageways
  • Visible debris collected inside the probe

Check in this order

  1. Remove power from the sensor probe by disconnecting the 24V supply wire from its transformer.
  2. Pull the sensor probe out of the ductwork and leave the mounting plate in place.
  3. Inspect the two passageways in the probe for visible particulate buildup.
  4. If nothing is visible, reinsert the probe into the mounting plate until it clicks. Do not push it past the click.
  5. If debris is visible, wet a cotton swab slightly with isopropyl or rubbing alcohol and gently wipe the internal surfaces of the probe. Then reinsert the probe until it clicks, without pushing past the click.
  6. Reconnect the 24V power to the sensor probe.
  7. Confirm the probe LED is solid blue, not flashing. Solid blue means the device is back online and operating.

Applies to: DSEN-HAQA Daikin One Home Air Monitor

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin One Home Air Monitor installation manual (IO-DSEN-HAQA), p. 4. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.