Cleaning the sensor probe
What is going on
Dirt inside the two air passageways of the sensor probe can make the particulate readings inaccurate. Only a qualified electrician or HVAC technician should do this. If you are not qualified, contact the HVAC dealer.
Likely causes
- Particulate buildup on the internal surfaces of the sensor probe passageways
- Visible debris collected inside the probe
Check in this order
- Remove power from the sensor probe by disconnecting the 24V supply wire from its transformer.
- Pull the sensor probe out of the ductwork and leave the mounting plate in place.
- Inspect the two passageways in the probe for visible particulate buildup.
- If nothing is visible, reinsert the probe into the mounting plate until it clicks. Do not push it past the click.
- If debris is visible, wet a cotton swab slightly with isopropyl or rubbing alcohol and gently wipe the internal surfaces of the probe. Then reinsert the probe until it clicks, without pushing past the click.
- Reconnect the 24V power to the sensor probe.
- Confirm the probe LED is solid blue, not flashing. Solid blue means the device is back online and operating.
Applies to: DSEN-HAQA Daikin One Home Air Monitor
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin One Home Air Monitor installation manual (IO-DSEN-HAQA), p. 4. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.