Trane · Air handler troubleshooting
Reading and clearing fault history - Trane P0V0 modular blower
What is going on
Use this when you need to read or clear the stored fault history on a Trane P0V0 modular blower. The control works with the same button logic as the furnace control, so if you know one you know the other. Look at the history before you change anything, because the past faults tell you what the unit has been fighting. Only clear them after the repair is done and confirmed.
Likely causes
- Old faults stored in memory after a repair
- Intermittent problem and you need the last faults
- Startup or commissioning check
- Factory reset needed after a control change
Check in this order
- Scroll with Menu to 'err' for active alarms or 'L6F' for the last 6 faults, press Option to enter
- Write down the faults before erasing so you do not lose the information
- Hold Option at least 5 s inside L6F to erase, three dashes 3 times confirms
- Factory reset at idle hold Menu + Option 15 s until 'FD' flashes 3 times
- Run test (run menu) cycles the blower at 1st then 2nd stage compressor airflow for 30 s each, three times
- The run test does not start the outdoor unit and takes about 70 s to begin, so be patient
- Power off before touching any wiring
Applies to: Trane P0V0 modular blowers (P0V0A/B/C/D)
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Trane 18-GE20D1-1E-EN - section Fault Code Recovery / IMBC Menu. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.