Lennox · Air conditioner troubleshooting
Outdoor unit will not start - Lennox EL16KC1
What is going on
Thermostat calls for cooling but the compressor and outdoor fan do not run.
Likely causes
- No 24 VAC Y1 call or common
- High pressure switch open
- Low pressure switch open
- Timed-off control (A4) delay, if installed
- Refrigerant detection system (RDS) in leak mode
- Contactor or line voltage problem
Check in this order
- Check 24 VAC between Y1 (yellow) and C (black) at the outdoor unit wire connections.
- If an A4 timed-off control is used, wait out its delay; Y1 goes to A4 terminal 2 and S4 to terminal 3.
- Test high pressure switch S4 it should open at 590 +/- 10 psig and close again at 418 +/- 5 psig.
- Check the low pressure switch S87 (opens at 40 +/- 5 psig, resets at 90 +/- 5 psig); a low charge will hold it open.
- Check that contactor K1 pulls in and line voltage is within the nameplate range.
- If the RDS board LED is flashing blue, the system is in leak mitigation and keeps the compressor off - find the leak or sensor issue first.
- Crankcase heater should be powered 24 hours before start-up.
Applies to: Lennox EL16KC1 (Elite) R-454B air conditioners, sizes -018 to -060
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Lennox EL16KC1 Unit Information Corp. 100121 (01-2025), System Operation p.27, Typical Field Wiring pp.30-31, Start-Up p.32, Start-Up Test Procedure p.36. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.