KeepRite · Air conditioner troubleshooting

Checking OAT and OCT thermistors - KeepRite C4A3/CXA6

What is going on

How to check the outdoor air and coil thermistors behind codes 53, 55 and 56.

Likely causes

  • Failed thermistor
  • Sensor moved from its factory location
  • Loose OCT clamp

Check in this order

  1. Unplug the thermistor assembly from the board.
  2. Measure each thermistor and compare with the resistance curve (about 16,000 ohms at 60°F).
  3. Check the OAT is locked in its keyhole in the control box shelf.
  4. Check the OCT (C4A3 sizes 24 and 30) is fastened tightly on the liquid tube.
  5. Replace any sensor out of range. The board falls back to default operation if a sensor fails.

Applies to: KeepRite C4A3/CXA6 AC with outdoor control board

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: KeepRite/ICP C4A3/H4A3/T4A3/CXA6 Installation Instructions 421 01 5103 05, Temperature Thermistors p.16, Fig. 17-18 p.14 and p.18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.