KeepRite · Air conditioner troubleshooting

Checking OAT and OCT thermistors - KeepRite C4A3/CXA6

What is going on

Codes 53, 55 and 56 on the KeepRite C4A3 or CXA6 point to the outdoor air thermistor (OAT) or the outdoor coil thermistor (OCT). These are simple sensors, and you can check them with an ohmmeter. A thermistor is a resistor that changes value with temperature, so you compare your reading to the curve for the ambient. The usual trouble is a sensor that has been moved from its factory spot. If a sensor fails, the board falls back to default operation, so the system keeps running but not optimally.

Likely causes

  • Failed thermistor
  • Sensor moved from its factory location
  • Loose OCT clamp
  • Damaged wire or plug at the board

Check in this order

  1. Unplug the thermistor assembly from the board, power off first
  2. Measure each thermistor and compare with the resistance curve (about 16,000 ohms at 60°F)
  3. Check the OAT is locked in its keyhole in the control box shelf
  4. Check the OCT (C4A3 sizes 24 and 30) is fastened tightly on the liquid tube, a loose clamp reads the wrong temperature
  5. Inspect the wire and plug for damage
  6. Replace any sensor out of range
  7. The board falls back to default operation if a sensor fails, so do not ignore the code

Applies to: KeepRite C4A3/CXA6 AC with outdoor control board

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: KeepRite/ICP C4A3/H4A3/T4A3/CXA6 Installation Instructions 421 01 5103 05, Temperature Thermistors p.16, Fig. 17-18 p.14 and p.18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.