Viessmann · Mini-split
ODU E6 PFC module protection (outdoor board)
What the control is telling you
Outdoor board display; also shown when PFC protection happens 3 times in 15 minutes. Indoor shows PC0F.
Applies to: DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
Test and repair steps
- Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
- Check the cable between the main board and the PFC (IPM) module.
- Measure DC across P and N on the IPM 277-356 V for 18-27K, 277-410 V for 36K.
- Check the PFC inductor the two leads should read about 0 ohms. Open = replace the inductor.
- Still faulty replace the PFC (IPM) module, then the outdoor main board.
Models that show this code
7 models in Viessmann Vitocal 200-S DLCM(R/H)B multi-zone outdoor
Other codes on the same units
- ODU E2 Indoor / outdoor communication error (outdoor board)
- ODU E3 IPM to main board communication error (outdoor board)
- ODU E4 Outdoor or T2B sensor fault (outdoor board)
- ODU E5 Over or under voltage (outdoor board)
- ODU E8 Outdoor fan speed fault (outdoor board)
- ODU Ed Adapter / inverter board to main board communication error
- ODU F1 Zone A coil outlet sensor (T2B-A) fault
- ODU F2 Zone B coil outlet sensor (T2B-B) fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Table 27 Outdoor Unit Digital Codes p.32; diagnosis p.56-57. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.