Viessmann · Mini-split

ODU E4 Outdoor or T2B sensor fault (outdoor board)

Medium severity Viessmann Vitocal 200-S DLCM(R/H)B multi-zone outdoor

What the control is telling you

One of T3, T4, T5 or a T2B sensor is open or shorted. Indoor shows EC52/EC53/EC54/EC56 (old F2/F1/F3/F6).

Applies to: DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)

Test and repair steps

  1. Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
  2. Check the sensor plug on the board and the wire for damage.
  3. Unplug the sensor and measure its resistance. T1-T4 sensors read about 10 kOhm at 77 F (25 C); the discharge sensor (T5/TP) about 54.9 kOhm at 77 F. Compare with the sensor resistance tables.
  4. Out of range or open/shorted replace the sensor. Sensor reads fine: replace the board it plugs into.

Models that show this code

7 models in Viessmann Vitocal 200-S DLCM(R/H)B multi-zone outdoor

DLCMHBH24CAKDLCMHBH30DAKDLCMHBH36DAKDLCMHBH48EAKDLCMRBH18BAKDLCMRBH36DAKDLCMRBH48EAK

Other codes on the same units

  • ODU CE Automatic wiring / piping check running
  • ODU E0 Outdoor EEPROM error (outdoor board)
  • ODU E2 Indoor / outdoor communication error (outdoor board)
  • ODU E3 IPM to main board communication error (outdoor board)
  • ODU E5 Over or under voltage (outdoor board)
  • ODU E6 PFC module protection (outdoor board)
  • ODU E8 Outdoor fan speed fault (outdoor board)
  • ODU Ed Adapter / inverter board to main board communication error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Table 27 Outdoor Unit Digital Codes p.32; diagnosis p.51. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.