Viessmann · Mini-split
EC54 Discharge temperature sensor (TP/T5) fault
What the control is telling you
Compressor discharge sensor open or shorted.
Applies to: DLCM(R/H)B multi-zone outdoor units with DLFSHBH high wall indoor units (Midea, Carrier, Viessmann)
Likely causes
- Sensor plug loose
- Bad discharge sensor
- Bad outdoor PCB
Test and repair steps
- Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
- Check the sensor plug on the board and the wire for damage.
- Unplug the sensor and measure its resistance. T1-T4 sensors read about 10 kOhm at 77 F (25 C); the discharge sensor (T5/TP) about 54.9 kOhm at 77 F. Compare with the sensor resistance tables.
- Out of range or open/shorted replace the sensor. Sensor reads fine: replace the board it plugs into.
Models that show this code
12 models in Viessmann Vitocal 200-S DLCM(R/H)B multi-zone outdoor, Viessmann DLFSHB high wall indoor
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Table 23 Outdoor Unit Error Display p.26; diagnosis p.40, 51; Carrier MS-DLFSHB-01 High Wall Ductless Service Manual (04/2021), Table 9 p.17. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.