PC40 Communication error between outdoor main chip and compressor driven chip
What the control is telling you
The main chip cannot detect the compressor driven chip.
Applies to: DLCSRB outdoor units, sizes 06 to 36
Likely causes
- Faulty outdoor PCB
- Faulty electric control box
Test and repair steps
- Turn off the power and wait 2 minutes, then turn it back on.
- If the code still shows, replace the outdoor main board.
- If the system still does not run normally, replace the electric control box.
Models that show this code
22 models in Vitocal 100-S, DLCSRB
Other codes on the same units
- PC11 Main control board DC bus high voltage protection
- PC12 Main control board DC bus high voltage protection / 341 MCE error
- PC30 System high pressure protection
- PC31 System low pressure protection
- PC42 Compressor start failure
- PC43 Outdoor compressor lack phase protection
- PC44 Outdoor unit zero speed protection
- PC45 Outdoor unit IR chip drive failure
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitocal 100-S DLCSRB service manual, p. 46. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.