Viessmann · Boiler
LED OFF Coco OT LED off, no BUS communication
What the control is telling you
The Coco OT LED is off, which means there is no BUS communication.
Applies to: Coco OT module LED indicator
Likely causes
- No BUS communication between the control and the Coco OT module.
Test and repair steps
- Check the 4-conductor CAN wiring between the Versatronik 200 and the Coco OT.
- Check that CAN H and CAN L are not reversed.
- Check the power supply terminals on the Coco OT.
Other codes on the same units
- C 24 hour reduced heating operation
- HO Holiday operation
- LED 1s ON / 3s OFF Coco OT no CAN communication
- LED 3s ON / 1s OFF Coco OT no OT communication
- LED ON Coco OT LED on, communication good
- PL Expert level active
- i Stand-by operating mode
- j Service operation
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Versatronik 200 installation and operating manual, p. 19. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.