Viessmann · Boiler
F Fb Combustion chamber pressure too high, burner not starting
What the control is telling you
Burner does not start because combustion chamber pressure is too high, and the burner control unit is in a fault state.
Applies to: CA3B Series 2.5 to 6.0
Likely causes
- Flue gas path or condensate path blocked
- Excessive combustion chamber pressure at air pressure switch 2 (LDW2)
- Motorized burner damper does not open or close
Test and repair steps
- Check the flue gas path or condensate path and clean if required.
- Check the motorized burner damper.
Models that show this code
23 models in Vitocrossal 300 CA3B
Other codes on the same units
- F EA Main gas valve leaking (multiple gas types)
- F EC Fault around burner control unit (internal or EMC)
- F Eb Burner blocked by external device
- F Ed Fault around burner control unit (internal or EMC)
- F FA Fan runs without demand
- F FF Fault around burner control unit (internal or EMC)
- F Fd Fault around burner control unit (internal or EMC)
- F d0 Multiple gas types selected
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocrossal 300 CA3B service instructions, p. 31. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.