F.543 Heating circuit 1 supply sensor short circuit, emergency mode
What the control is telling you
Emergency mode is active for heating circuit 1. The heating circuit pump runs and the mixing valve moves to CLOSED.
Applies to: Vitocrossal 200 CI2 boiler, heating circuit 1
Likely causes
- Short circuit, supply temperature sensor, heating circuit 1
Test and repair steps
- Check the supply temperature sensor and mixing valve 1.
- Measure the sensor input on the electronics module with the sensor disconnected (target 3.3V DC).
Models that show this code
21 models in Vitocrossal 200 CI2
Other codes on the same units
- F.519 BACnet communication error with building management system
- F.520 Modbus communication error with building management system
- F.541 No feedback from flue gas damper
- F.542 Heating circuit 1 supply sensor lead break, emergency mode
- F.575 Room temperature sensor lead break, heating circuit 1
- F.576 Room temperature sensor short circuit, heating circuit 1
- F.577 Room temperature sensor for heating circuit 2 not available
- F.578 Room temperature sensor lead break, heating circuit 2
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocrossal 200 CI2 service instructions, p. 67. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.