Viessmann · Boiler

F.477 Solar differential temperature monitoring

Low severity Vitodens 200-W B2HE

What the control is telling you

Limited solar functionality.

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Likely causes

  • Solar circuit, pump or sensor fault

Test and repair steps

  1. Check solar circuit, solar pump and sensors.

Models that show this code

3 models in Vitodens 200-W B2HE

B2HE-120B2HE-150B2HE-85

Other codes on the same units

  • F.468 Ionization current too high during calibration
  • F.471 Sensor circuit fault (call for heat)
  • F.473 HMU communication error
  • F.474 Program run monitoring error
  • F.49 Flue gas temperature sensor open circuit
  • F.5 Sensor circuit fault at plug 33 (X6)
  • F.50 Flue gas temperature sensor short circuit
  • F.517 Remote control not working

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.