Viessmann · Boiler

cEe Plug-in adaptor for external safety equipment communication error

Medium severity Vitotronic 100

What the control is telling you

Controlled operation.

Applies to: Vitotronic 100 GC1 boiler control

Likely causes

  • Communication fault with the plug-in adaptor for external safety equipment.

Models that show this code

2 models in Vitotronic 100

GC1KW10B

Other codes on the same units

  • 12 u Service message: time interval reached
  • 09572 h Burner hours run, 2nd stage
  • 30417 Burner starts
  • 35510 h Service message: burner hours reached
  • 63572 h Burner hours run, 1st stage
  • a 245 Service message: maximum flue gas temperature reached (°C)
  • aCc Return temperature sensor configuration error
  • aCd Butterfly valve configuration error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 103. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.