Viessmann · Boiler

8E Failure boiler 3

High severity Versatronik 300

What the control is telling you

Boiler 3 has failed.

Applies to: Versatronik 300 cascade control

Other codes on the same units

  • 5C Failure boiler 5
  • 5D Failure boiler 6
  • 5E Failure boiler 7
  • 5F Failure boiler 8
  • 8C Failure boiler 1
  • 8D Failure boiler 2
  • 8F Failure boiler 4
  • 9E Solarmodule delta-T monitoring failure, solar control

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Versatronik 300 Cascade Control manual, p. 40. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.