Viessmann · Boiler

7 70 Return temperature sensor short circuit (outdoor reset without return sensor)

Medium severity Vitotronic 200-H

What the control is telling you

Return temperature sensor is shorted. Applies to outdoor reset logic in the control unit without a return temperature sensor.

Applies to: Vitotronic 200-H, Model HK1M

Likely causes

  • Short circuit in the return temperature sensor

Test and repair steps

  1. Check the return temperature sensor (see page 35).
  2. If no return temperature sensor is fitted, set coding 4b to 0.

Models that show this code

6 models in Vitotronic 200-H

HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300

Other codes on the same units

  • 1 10 Outdoor temperature sensor short circuit
  • 1 18 Outdoor temperature sensor cable break
  • 2 20 Supply temperature sensor short circuit
  • 2 28 Supply temperature sensor cable break
  • 7 78 Return temperature sensor cable break (outdoor reset without return sensor)
  • E e0 Viessmann 2-wire BUS communication module cable break
  • b b1 Programming unit communication fault
  • b b4 Undefined control characteristics: internal electronics fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitotronic 200-H installation and service instructions, p. 29. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.