Viessmann · Boiler
01 to 97 LON participant fault
What the control is telling you
A fault has occurred at a LON participant (for example 12 for Vitotronic 200-H), or there is no connection to the participant. Requires the control unit to be programmed as fault manager (code "79:1").
Applies to: Vitotronic 300-K LON system
Likely causes
- Fault at LON participant
- No connection to the LON participant
Test and repair steps
- Download fault code to participant.
- Check coding.
- Check connecting LON cable.
- Update the LON participant list.
- Carry out a participant check.
Models that show this code
6 models in Vitotronic 200, Vitotronic 300-K
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitotronic 200 and 300-K installation and service instructions, p. 77. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.