Viessmann · Air handler

FL 09 Indoor and outdoor unit mismatch

Medium severity Vitocal IND-A

What the control is telling you

The indoor and outdoor units are mismatched and the LED shows this code. Replace the matching indoor or outdoor unit.

Applies to: DLFUAA indoor air handler (Vitocal IND-A)

Likely causes

  • Indoor unit does not match the outdoor unit
  • Loose or faulty wiring or connections
  • Faulty outdoor main control board or indoor main PCB

Test and repair steps

  1. Turn the power off, then restart the unit after 3 minutes.
  2. If the error still exists, replace the outdoor main control board.
  3. Check the wiring and connections, and make sure all connections are good.
  4. If the connections are good and the fault remains, replace the indoor main PCB.

Models that show this code

14 models in Vitocal IND-A

DLFLABH36XA3DLFLABH48XA3DLFLABH60XA3DLFSABH18XB3DLFSABH24XB3DLFSABH30XB3DLFSABH36XB3DLFUAAQ18XB3DLFUAAQ24XB3DLFUAAQ30XB3DLFUAAQ36XA3DLFUAAQ36XB3DLFUAAQ48XA3DLFUAAQ60XA3

Other codes on the same units

  • EH 0b Communication error between the two indoor chips
  • EL 16 Communication malfunction between adapter board and outdoor main board

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLFUAA service manual, p. 33. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.