Trane · Heat pump

Fault history mode Fault history diagnostics mode

Menu / mode display Trane 5TWR7

What the display is showing

The manual says the digital display offers a diagnostics mode that cycles through historical faults, but does not give the entry steps in the text. Multiple active faults cycle automatically.

Applies to: 5TTR7 A-C / 5TWR7 heat pump multi-speed outdoor drive (AOC)

Settings for these units

Outdoor unit placement · Trane 5TWR7

ItemValue
Above unit5 ft clear
Service side3 ft
Walls / shrubs12 in. min
Pad1 in. larger than unit all round, level, separate from house
Cold climate (HP)raise 3-12 in. above pad
Within 1 mile of salt wateradd BAYSEAC001 if no factory salt shield
Operating rangecooling 55-120 F, heating 0-66 F

Avoid bedroom walls and under roof drip lines.

Dimensions and weights · Trane 5TWR7

ModelH x D x W (in.)Weight (lb)
5TWR7024A41 x 30 x 33181
5TWR7036A41 x 30 x 33194
5TWR7048A41 x 34 x 37231
5TWR7060A41 x 34 x 37241
5TTR7024A41 x 30 x 33176
5TTR7036A41 x 30 x 33189
5TTR7048A41 x 34 x 37226
5TTR7060A41 x 34 x 37236

Weights are estimated, uncrated.

Models that show this code

4 models in Trane 5TWR7

5TWR7024A5TWR7036A5TWR7048A5TWR7060A

Other codes on the same units

  • Y2 Running, high speed (A1000BA)
  • Y2. Running, boost speed (A1000BA)
  • FA Outdoor ambient sensor fault
  • FC Coil temperature sensor fault
  • Fd Discharge temperature sensor fault
  • Force defrost button Force a defrost cycle
  • Fr No 24 VAC R signal at outdoor control (heat pump)
  • HC Hard lock: compressor over-current

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Trane 5TTR7/5TWR7 installation ODR-SVN002E-EN, Tables 17-18 notes, p.24-26. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.