Trane · Heat pump
FA Outdoor ambient sensor fault
What the control is telling you
Ambient temperature sensor out of range. Manual lists only the meaning (A1000BA board); steps are general checks drawn from other sections of the guide.
Applies to: Trane 5TWR7 multi-speed heat pump (5TWR7024A-060A)
Likely causes
- Sensor unplugged or damaged wire
- Failed sensor
Test and repair steps
- Locate the sensor plug on the control board (J21 ambient, J23 coil, J22 discharge).
- Check the plug is seated and the wire is not damaged.
- Check the sensor is clipped in its proper location.
- Replace the sensor if it reads open or shorted.
Settings for these units
Outdoor unit placement · Trane 5TWR7
| Item | Value |
|---|---|
| Above unit | 5 ft clear |
| Service side | 3 ft |
| Walls / shrubs | 12 in. min |
| Pad | 1 in. larger than unit all round, level, separate from house |
| Cold climate (HP) | raise 3-12 in. above pad |
| Within 1 mile of salt water | add BAYSEAC001 if no factory salt shield |
| Operating range | cooling 55-120 F, heating 0-66 F |
Avoid bedroom walls and under roof drip lines.
Dimensions and weights · Trane 5TWR7
| Model | H x D x W (in.) | Weight (lb) |
|---|---|---|
| 5TWR7024A | 41 x 30 x 33 | 181 |
| 5TWR7036A | 41 x 30 x 33 | 194 |
| 5TWR7048A | 41 x 34 x 37 | 231 |
| 5TWR7060A | 41 x 34 x 37 | 241 |
| 5TTR7024A | 41 x 30 x 33 | 176 |
| 5TTR7036A | 41 x 30 x 33 | 189 |
| 5TTR7048A | 41 x 34 x 37 | 226 |
| 5TTR7060A | 41 x 34 x 37 | 236 |
Weights are estimated, uncrated.
Models that show this code
4 models in Trane 5TWR7
Other codes on the same units
- L8 Lockout: high coil temperature
- Y1 Running, low speed (A1000BA)
- Y2 Running, high speed (A1000BA)
- Y2. Running, boost speed (A1000BA)
- FC Coil temperature sensor fault
- Fault history mode Fault history diagnostics mode
- Fd Discharge temperature sensor fault
- Force defrost button Force a defrost cycle
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Trane ODR-SVN002E-EN (5TTR7/5TWR7 installer's guide) - section Integrated Variable Speed Control Board LED Indicators, Table 18 (A1000BA models). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.