Trane · Heat pump
2nd digit E High drive PFC temperature protection (A1000AA board)
What the control is telling you
On A1000AA boards the right-hand 7-segment digit shows the fault and the left digit shows status; this value means: high drive pfc temperature protection. Manual gives only the meaning; steps are general checks.
Applies to: Trane 5TWR7 multi-speed heat pump (5TWR7024A-060A) with A1000AA control
Likely causes
- Blocked airflow over drive/coil
- Dirty coil
- Very high ambient
- Fan problem
Test and repair steps
- Warning: After power off, wait 2 minutes - the inverter can hold 400 VDC. Confirm under 42 VDC at the +DC/-DC test points before touching the board.
- Check that the drive heat sink and outdoor coil are clean and airflow is not blocked (5 ft above, 12 in. from walls).
- Check the outdoor fan runs at speed.
- Confirm high ambient is not above the 120 F cooling limit.
Settings for these units
Outdoor unit placement · Trane 5TWR7
| Item | Value |
|---|---|
| Above unit | 5 ft clear |
| Service side | 3 ft |
| Walls / shrubs | 12 in. min |
| Pad | 1 in. larger than unit all round, level, separate from house |
| Cold climate (HP) | raise 3-12 in. above pad |
| Within 1 mile of salt water | add BAYSEAC001 if no factory salt shield |
| Operating range | cooling 55-120 F, heating 0-66 F |
Avoid bedroom walls and under roof drip lines.
Dimensions and weights · Trane 5TWR7
| Model | H x D x W (in.) | Weight (lb) |
|---|---|---|
| 5TWR7024A | 41 x 30 x 33 | 181 |
| 5TWR7036A | 41 x 30 x 33 | 194 |
| 5TWR7048A | 41 x 34 x 37 | 231 |
| 5TWR7060A | 41 x 34 x 37 | 241 |
| 5TTR7024A | 41 x 30 x 33 | 176 |
| 5TTR7036A | 41 x 30 x 33 | 189 |
| 5TTR7048A | 41 x 34 x 37 | 226 |
| 5TTR7060A | 41 x 34 x 37 | 236 |
Weights are estimated, uncrated.
Models that show this code
4 models in Trane 5TWR7
Other codes on the same units
- 2nd digit 8 High discharge temperature protection (A1000AA board)
- 2nd digit 9 High drive compressor IPM temperature (A1000AA board)
- 2nd digit A Outdoor ambient sensor fault (A1000AA board)
- 2nd digit C Coil temperature sensor fault (A1000AA board)
- 2nd digit F High drive fan IPM temperature protection (A1000AA board)
- 2nd digit P Pressure protection (high or low) (A1000AA board)
- 2nd digit b AOC jumper pin engaged (A1000AA board)
- 2nd digit d Discharge temperature sensor fault (A1000AA board)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Trane ODR-SVN002E-EN (5TTR7/5TWR7 installer's guide) - section Integrated Variable Speed Control Board LED Indicators, Table 17 (A1000AA models). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.