Trane · Heat pump

2nd digit 9 High drive compressor IPM temperature (A1000AA board)

High severity Trane 5TWR7

What the control is telling you

On A1000AA boards the right-hand 7-segment digit shows the fault and the left digit shows status; this value means: high drive compressor ipm temperature. Manual gives only the meaning; steps are general checks.

Applies to: Trane 5TWR7 multi-speed heat pump (5TWR7024A-060A) with A1000AA control

Likely causes

  • Blocked airflow over drive/coil
  • Dirty coil
  • Very high ambient
  • Fan problem

Test and repair steps

  1. Warning: After power off, wait 2 minutes - the inverter can hold 400 VDC. Confirm under 42 VDC at the +DC/-DC test points before touching the board.
  2. Check that the drive heat sink and outdoor coil are clean and airflow is not blocked (5 ft above, 12 in. from walls).
  3. Check the outdoor fan runs at speed.
  4. Confirm high ambient is not above the 120 F cooling limit.

Settings for these units

Outdoor unit placement · Trane 5TWR7

ItemValue
Above unit5 ft clear
Service side3 ft
Walls / shrubs12 in. min
Pad1 in. larger than unit all round, level, separate from house
Cold climate (HP)raise 3-12 in. above pad
Within 1 mile of salt wateradd BAYSEAC001 if no factory salt shield
Operating rangecooling 55-120 F, heating 0-66 F

Avoid bedroom walls and under roof drip lines.

Dimensions and weights · Trane 5TWR7

ModelH x D x W (in.)Weight (lb)
5TWR7024A41 x 30 x 33181
5TWR7036A41 x 30 x 33194
5TWR7048A41 x 34 x 37231
5TWR7060A41 x 34 x 37241
5TTR7024A41 x 30 x 33176
5TTR7036A41 x 30 x 33189
5TTR7048A41 x 34 x 37226
5TTR7060A41 x 34 x 37236

Weights are estimated, uncrated.

Models that show this code

4 models in Trane 5TWR7

5TWR7024A5TWR7036A5TWR7048A5TWR7060A

Other codes on the same units

  • 2nd digit 5 Outdoor fan over-current protection (A1000AA board)
  • 2nd digit 6 High preheat IPM temperature (A1000AA board)
  • 2nd digit 7 High coil temperature protection (A1000AA board)
  • 2nd digit 8 High discharge temperature protection (A1000AA board)
  • 2nd digit A Outdoor ambient sensor fault (A1000AA board)
  • 2nd digit C Coil temperature sensor fault (A1000AA board)
  • 2nd digit E High drive PFC temperature protection (A1000AA board)
  • 2nd digit F High drive fan IPM temperature protection (A1000AA board)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Trane ODR-SVN002E-EN (5TTR7/5TWR7 installer's guide) - section Integrated Variable Speed Control Board LED Indicators, Table 17 (A1000AA models). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.