Trane · Air handler
CoF Continuous fan
What the display is showing
Display for a continuous-fan call. On a communicating-control setup it also reads CoF while the blower runs for cooling.
Applies to: P0V0 modular blower integrated control (IMBC)
Settings for these units
Return filter size by cabinet width · Trane P0V0
| Cabinet width | Filter |
|---|---|
| 14-1/2 in. | 1 - 14 x 25 x 1 in. |
| 17-1/2 in. | 1 - 16 x 25 x 1 in. |
| 21 in. | 1 - 20 x 25 x 1 in. |
| 24-1/2 in. | 1 - 24 x 25 x 1 in. |
No filter inside the unit - remote/duct filter required.
Over 1600 CFM needs dual returns.
Models that show this code
4 models in Trane P0V0
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Trane P0V0 modular blower installer's guide 18-GE20D1-1E-EN, IMBC Display Codes, p.30; field wiring notes, p.26. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.