Trane · Air handler

FD Factory default reset done

Menu / mode display Trane P0V0

What the display is showing

The display flashes FD three times to confirm that the control was reset to factory defaults.

Applies to: P0V0 modular blower integrated control (IMBC)

What to do

  1. Display must be on IdL.
  2. Hold Menu and Option together for 15 seconds, then release.

Settings for these units

Return filter size by cabinet width · Trane P0V0

Cabinet widthFilter
14-1/2 in.1 - 14 x 25 x 1 in.
17-1/2 in.1 - 16 x 25 x 1 in.
21 in.1 - 20 x 25 x 1 in.
24-1/2 in.1 - 24 x 25 x 1 in.

No filter inside the unit - remote/duct filter required.

Over 1600 CFM needs dual returns.

Models that show this code

4 models in Trane P0V0

P0V0A000M30SCAP0V0B000M40SCAP0V0C000M50SCAP0V0D000M50SCA

Other codes on the same units

  • L6F Last 6 faults menu
  • --- Faults cleared confirmation
  • CoF Continuous fan
  • Cr Code release number
  • IdL Idle - no thermostat demand
  • aRF Calculated airflow readout (cfm x 10)
  • err Active alarm menu
  • run Run test mode

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Trane P0V0 modular blower installer's guide 18-GE20D1-1E-EN, Fault Code Recovery, Resetting Factory Defaults, p.31. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.