Rinnai · Tankless water heater
10 Air supply or exhaust blocked / condensate trap full
What the control is telling you
The unit detects restricted combustion air intake or exhaust. On SENSEI and SENSEI RX/CX units, it also triggers when a blocked condensate drain backs up into the internal trap.
Applies to: SENSEI, SENSEI RX/CX and non-SENSEI tankless (condensate trap check: SENSEI and SENSEI RX/CX only)
Likely causes
- Clogged or frozen condensate drain line backing up the internal trap (SENSEI, SENSEI RX/CX)
- Dirty inlet air filter
- Vent installed wrong: unapproved materials, poorly seated or unsealed joints, too long, bad clearances
- Vent pipe crushed by foam sealant, or debris/water/insects inside the vent
- Fan wheel, housing, air duct or check valve restricted or stuck
- Debris in the burner, or blocked heat exchanger fins
- Incorrect altitude parameter, manifold gas pressures or DIP switch settings
- Faulty fan motor/bearing, fan wiring harness or PC Board
Test and repair steps
- SENSEI/RX/CX Make sure the condensate line drains. A blocked or frozen line backs up into the internal trap and triggers code 10. Then clean the inlet air filter (top right, under the front cover).
- All Inspect the whole intake and exhaust system inside and out: clearances, approved vent materials for this model, and joints fully seated and sealed.
- Warning: Never leave the heater running with intake or exhaust disconnected. The next step is a test only. Reconnect the vent right away.
- All (only if it codes out while you are there): Disconnect the exhaust from the top of the unit and run hot water. If it runs without the code, the restriction is in the vent system.
- If it still codes out mark each vent joint, take the vent apart and check insertion depth. Reassemble with the vent supplier's lubricant. Bad joints can leak exhaust and cause code 10.
- Confirm equivalent vent length is within limits (concentric: 90° elbow = 6 ft, 45° = 3 ft). Non-SENSEI: also set the vent-length DIP switches to match.
- Make sure foam sealant at the wall penetration has not crushed the pipe (check with a flashlight or camera). Open joints and look for water, condensation, insects or debris.
- Confirm termination clearances to other vent terminals and to overhangs, grade, walls, porches and obstructions, per the venting instructions.
- Caution: Turn off power. Remove the fan and check the wheel, housing and air duct for restrictions. SENSEI: also make sure the check valve behind the fan is not stuck. Refit the fan and test.
- SENSEI/RX/CX Confirm the high altitude parameter. Non-SENSEI (gas-qualified only): confirm low/high fire manifold pressures and altitude DIP switches. A wrong setting can trigger code 10 via the burner sensor.
- Non-SENSEI – WARNING (VE, VA, VB, VC, KA, RH-180, KCM): Turn off power, gas and water. Clear the manifold orifices and burner chamber, then blow out fins at 120 psi (wear glasses/mask) or replace the heat exchanger.
- SENSEI/RX/CX – WARNING: Turn off power, gas and water before removing the heat exchanger assembly.
- SENSEI/RX/CX Separate the burner, clean debris from the burner and air chamber, and check the back of the burner. Do NOT blow out the burner with compressed air. Blow out heat exchanger fins at 120 psi or replace.
- Warning: Disconnect power and gas before replacing parts. Other possible causes: faulty fan motor or bearing, fan wiring harness, PC Board, or wrong DIP switch settings (non-SENSEI).
Settings for these units
RSC supply connection sizes · SENSEI
| Connection | Size |
|---|---|
| Gas | 3/4 in. NPT |
| Cold inlet | 3/4 in. NPT |
| Hot outlet | 3/4 in. NPT |
| Condensate drain | 1/2 in. NPT |
| Pressure relief valve | M33 thread |
The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.
Condensate drain line must stay at least 1/2 in. over its whole length.
RSC water quality limits · SENSEI
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg/L |
| Aluminum | Up to 0.2 mg/L |
| Chlorides | Up to 250 mg/L |
| Copper | Up to 1.0 mg/L |
| Dissolved CO2 | Up to 15.0 mg/L |
| Iron | Up to 0.3 mg/L |
| Manganese | Up to 0.05 mg/L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg/L |
| Zinc | Up to 5 mg/L |
Damage from water above these limits is not covered by warranty.
Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.
- RSC clearances to combustibles · SENSEI
- RSC temperature settings available · SENSEI
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
Models that show this code
97 models in Non-SENSEI, RH180 hybrid, SENSEI RX/CX, SENSEI
Other codes on the same units
- 03 Power interrupted during bath fill
- 05 Bypass flow control device fault
- 07 Circulation flow rate below 2.1 GPM
- 11 No ignition
- 11 (VA, VB, VC, KA, RH-180, KCM alternate checks) Code 11 - alternate checks for VA, VB, VC, KA, RH-180 and KCM
- 12 Flame failure
- 13 Combustion fault
- 14 Thermal fuse or overheat sensor tripped
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.12–15. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.