Rinnai · Tankless water heater
03 Power interrupted during bath fill
What the control is telling you
Power to the water heater was lost while a bath fill was in progress.
Applies to: SENSEI, SENSEI RX/CX and non-SENSEI tankless
Likely causes
- Power supply was interrupted during a bath fill
- Faulty PC Board, if the code keeps returning after resets
Test and repair steps
- Close all hot water fixtures.
- Press the ON/OFF button on the controller twice to clear the code.
- If the code comes back after three resets, replace the PC Board.
Settings for these units
RSC supply connection sizes · SENSEI
| Connection | Size |
|---|---|
| Gas | 3/4 in. NPT |
| Cold inlet | 3/4 in. NPT |
| Hot outlet | 3/4 in. NPT |
| Condensate drain | 1/2 in. NPT |
| Pressure relief valve | M33 thread |
The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.
Condensate drain line must stay at least 1/2 in. over its whole length.
RSC water quality limits · SENSEI
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg/L |
| Aluminum | Up to 0.2 mg/L |
| Chlorides | Up to 250 mg/L |
| Copper | Up to 1.0 mg/L |
| Dissolved CO2 | Up to 15.0 mg/L |
| Iron | Up to 0.3 mg/L |
| Manganese | Up to 0.05 mg/L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg/L |
| Zinc | Up to 5 mg/L |
Damage from water above these limits is not covered by warranty.
Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.
- RSC clearances to combustibles · SENSEI
- RSC temperature settings available · SENSEI
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
Models that show this code
97 models in Non-SENSEI, RH180 hybrid, SENSEI RX/CX, SENSEI
Other codes on the same units
- 02 Burner did not operate during freeze protection
- 05 Bypass flow control device fault
- 07 Circulation flow rate below 2.1 GPM
- 10 Air supply or exhaust blocked / condensate trap full
- 11 No ignition
- 11 (VA, VB, VC, KA, RH-180, KCM alternate checks) Code 11 - alternate checks for VA, VB, VC, KA, RH-180 and KCM
- 12 Flame failure
- 13 Combustion fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.9. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.