Rinnai · Combi boiler

999 PC Board / software mismatch

High severity I-Series Plus 150K and smallerI-Series Plus 175K and higher

What the control is telling you

The PC Board and the internal logic do not match.

Applies to: I-Series Plus boilers — 150K BTU and smaller and 175K BTU and higher (Combi and Solo)

Likely causes

  • Harnesses connected to the wrong terminals
  • Wet or corroded board connections
  • Software version mismatch between PC Board and operation board
  • Failed PC Board

Test and repair steps

  1. Confirm every wiring harness is plugged into the correct terminal.
  2. Inspect PC Board connections for moisture or corrosion.
  3. Check that PC Board and operation board software versions match; replace whichever component doesn't match.
  4. Replace the PC Board if the fault remains.
  5. Before swapping the PC Board, write down all parameter settings, then copy them from the old board using the data transfer cable supplied with the new board (see the part's instructions).
  6. If data transfer fails, re-program all parameters and set gas valve values per the Installation and Operation Manual (150K and smaller: also see docs 800000253 and 800000254).

Models that show this code

8 models in I-Series Plus 150K and smaller, I-Series Plus 175K and higher

IP060160CIP090099CIP090160CIP090199CIP120199CIP150199CIP175199CIP199199C

Other codes on the same units

  • 710 Gas solenoid circuit – valve position mismatch
  • 720 Flame rod fault
  • 763 0-10V external control input over-voltage
  • 890 Freeze condition detected
  • SW1-SW3 PC board buttons (SW1, SW2, SW3)
  • ECL Reset complete (gas solenoid circuit)
  • FFF Maintenance performed marker
  • LC Lime condition – flush plate heat exchanger

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting I-Series Plus Boiler Diagnostic Codes (800000375), p.45. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.