Rinnai · Combi boiler

890 Freeze condition detected

High severity I-Series Plus 150K and smallerI-Series Plus 175K and higher

What the control is telling you

At operation, the heat exchanger temperature reading is too low, indicating a possible freeze.

Applies to: I-Series Plus boilers — 150K BTU and smaller and 175K BTU and higher (Combi and Solo)

Likely causes

  • Frozen boiler lines, heat exchanger or CH system
  • Loose, broken or damaged thermistor wiring
  • Scale build-up on thermistor
  • Faulty thermistor
  • Failed PC Board

Test and repair steps

  1. Check that the boiler lines, heat exchanger and central heating system are not frozen.
  2. Inspect the thermistor harness back to the PC Board for loose, broken or damaged connections.
  3. With the boiler supply lines drained, remove the thermistor and clean off any scale.
  4. With water isolated, measure thermistor resistance on a 50K-ohm range at the thermistor side of the connector; warming the bulb (e.g., in your fingers) should lower resistance, and cooling it should raise it.
  5. Check at PC Board connector CN7 pins 7 and 10 and compare against Appendix A in the source manual (p.51); replace if off by more than 5°F.
  6. If readings are good, reinstall the thermistor with its small O-ring intact (lightly greased), turn water back on and check for leaks.
  7. Fire the unit; if 890 returns, check the whole system for frozen pipes. If nothing is frozen, replace the thermistor.
  8. If the code returns after a new thermistor, replace the PC Board.

Models that show this code

8 models in I-Series Plus 150K and smaller, I-Series Plus 175K and higher

IP060160CIP090099CIP090160CIP090199CIP120199CIP150199CIP175199CIP199199C

Other codes on the same units

  • 700 PC Board fault
  • 710 Gas solenoid circuit – valve position mismatch
  • 720 Flame rod fault
  • 763 0-10V external control input over-voltage
  • 999 PC Board / software mismatch
  • SW1-SW3 PC board buttons (SW1, SW2, SW3)
  • ECL Reset complete (gas solenoid circuit)
  • FFF Maintenance performed marker

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting I-Series Plus Boiler Diagnostic Codes (800000375), p.44. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.