Rinnai · Boiler

SS Service Soon reminder

Low severity I-Series Plus 150K and smallerI-Series Plus 175K and higher

What the control is telling you

Service reminder (when enabled in parameters) showing it is time to flush and service the boiler.

Applies to: I-Series Plus boilers — 150K BTU and smaller and 175K BTU and higher (Combi and Solo)

Likely causes

  • Service Soon reminder enabled in Parameter 04
  • Selected service interval has been reached

Test and repair steps

  1. Service and flush the boiler as needed.
  2. Reset SS by pressing the Central Heating (CH) button on the controller five times within five seconds.
  3. Confirm Parameter 04 is set to the desired interval: A = disabled, B = 0.5 year, C = 1 year, D = 2 years.
  4. SS will show again when the selected interval is reached next time.

Models that show this code

6 models in I-Series Plus 150K and smaller, I-Series Plus 175K and higher

IP060SIP090SIP120SIP150SIP175SIP199S

Other codes on the same units

  • SW1-SW3 PC board buttons (SW1, SW2, SW3)
  • ECL Reset complete (gas solenoid circuit)
  • FFF Maintenance performed marker
  • P Venturi reset: first screen
  • PCL Venturi reset accepted
  • Parameter mode Parameter settings menu
  • Perf data Performance data menu
  • SE Secondary unit error (cascade)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting I-Series Plus Boiler Diagnostic Codes (800000375), p.47. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.