Rinnai · Boiler

161 High outgoing temperature

High severity I-Series Plus 150K and smaller

What the control is telling you

Safety shutdown because the hot water outgoing temperature got too hot.

Applies to: IP060S, IP090S, IP120S, IP150S (Solo); listed for all I-Series Plus

Test and repair steps

  1. Turn off power at the disconnect before opening the unit.
  2. Check the outgoing thermistor wiring for damage.
  3. Measure the outgoing thermistor resistance.
  4. Check the gas valve for damage and that the correct orifice is installed.
  5. Replace the gas valve assembly if the other checks pass. Gas work: qualified gas technician only.

Models that show this code

4 models in I-Series Plus 150K and smaller

IP060SIP090SIP120SIP150S

Other codes on the same units

  • 110 Ignition failure
  • 120 Flame failure (flame lost during operation)
  • 140 Overheat switch tripped (heat exchanger overheating)
  • 150 Venturi control fault
  • 170 Venturi blockage / position mismatch
  • 180 Gas valve air/fuel adjustment limit reached
  • 190 Electrical grounding / short in DC circuit
  • 210 Data transfer error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai I-Series Plus Condensing Heat-Only Boiler Manual 800000191, Diagnostic Codes, PDF p.108. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.