Rheem · Furnace
61 Blower fault - blower not running
What the control is telling you
802P/R95P: main limit open more than 150 seconds during a heat call, so the control declares a dead blower and stops gas heat (61+22 while open, 61+10 during 1-hour lockout; 4th time in one call = hard lockout, reset by cycling the heat call). RGPE/RGLE: ECM blower not running (BLWR FLT-NO RUN), Call For Service.
Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); RGPE/RGLE 2-stage 80+
Likely causes
- Blower motor failed
- Bad blower capacitor (PSC models)
- No line voltage at blower
- Broken wiring between IFC and motor
- Severe airflow restriction
- RGPE/RGLE: no 24 V to ECM control, PFC choke problem
Test and repair steps
- 802P / R95P check line voltage between HEAT and NEUTRAL on the IFC during a heat call; check the blower capacitor.
- Check wiring and continuity between IFC and blower motor.
- RGPE/RGLE check 24 V at the ECM low-voltage connector pins 1 and 4, 115 VAC to the motor, and the PFC choke and its wiring.
- Check the blower motor and wheel; replace the motor if it does not run with correct power and signals.
- Check filter and ducts for restriction.
- Lockouts clear when the fault is fixed and power is cycled; a soft lockout can also be cleared by removing the heat call for more than 2 but less than 20 seconds.
Settings for these units
- Clearance to combustibles (all models) · R95P
- Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
- Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
- Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40-41, 51; R95P: Lockout section, p.88 (PDF p.92); RGPE/RGLE: Table 16 p.49 / Table 20; Fig. 45 p.63. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.