NTI · Boiler
Lockout 174 Safety relay feedback incorrect
What the control is telling you
Control board safety relay feedback does not match what the control commanded.
Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399
Likely causes
- Failing limit switch in the ILK circuit
- Control board hardware failure
Test and repair steps
- Check the internal low water cutoff and any external limit between R and LIM; replace if faulty
- Reset power; replace the control if the code returns
Models that show this code
13 models in Trinity Tft
Other codes on the same units
- Lockout 172 Main relay feedback incorrect
- Lockout 173 Pilot relay feedback incorrect
- Lockout 173 Pilot relay feedback incorrect
- Lockout 174 Safety relay feedback incorrect
- Lockout 175 Safety relay open
- Lockout 175 Safety relay open
- Lockout 176 Main relay ON at safe start check
- Lockout 176 Main relay ON at safe start check
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting, Table 16-3. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.