NTI · Boiler
Lockout 170 Safety relay opto feedback incorrect
What the control is telling you
Safety relay opto feedback incorrect.
Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399
Models that show this code
13 models in Trinity Tft
Other codes on the same units
- Lockout 165 Block intake OFF
- Lockout 169 Safety opto bad in test state
- Lockout 17 Internal fault: Safety relay test failed due to safety relay not OFF
- Lockout 17 Internal fault: Safety relay test failed due to safety relay not OFF
- Lockout 171 Safety relay feedback incorrect in run
- Lockout 172 Main relay feedback incorrect
- Lockout 172 Main relay feedback incorrect
- Lockout 173 Pilot relay feedback incorrect
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting, Table 16-3. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.