NTI · Boiler
Lockout 138 Flame too low
What the control is telling you
Flame signal is too weak for the control to keep the burner running.
Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399
Likely causes
- Blocked venting or air inlet
- Fouled or faulty flame sensor
- Combustion settings off
- Electrical noise on site
- Failing limit switch in the ILK circuit
Test and repair steps
- Check the exhaust, air inlet, blower, gas valve venturi and heat exchanger for blockage
- Inspect the flame sensor for cracks or fouling; clean or replace
- Recheck combustion readings and correct
- Look for sources of electrical noise such as a large motor starting at the same time
- Check the internal low water cutoff and any external limit between R and LIM
Models that show this code
13 models in Trinity Tft
Other codes on the same units
- Lockout 122 Light-off rate proving failed
- Lockout 122 Light off rate proving failed
- Lockout 123 Purge rate proving failed
- Lockout 123 Purge rate proving failed
- Lockout 143 Internal fault: Flame bias out of range 1
- Lockout 144 Internal fault: Flame bias out of range 2
- Lockout 145 Internal fault: Flame bias out of range 3
- Lockout 146 Internal fault: Flame bias out of range 4
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting, Table 16-3. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.