NTI · Boiler

Lockout 138 Flame too low

High severity Trinity Tft

What the control is telling you

Flame signal is too weak for the control to keep the burner running.

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

Likely causes

  • Blocked venting or air inlet
  • Fouled or faulty flame sensor
  • Combustion settings off
  • Electrical noise on site
  • Failing limit switch in the ILK circuit

Test and repair steps

  1. Check the exhaust, air inlet, blower, gas valve venturi and heat exchanger for blockage
  2. Inspect the flame sensor for cracks or fouling; clean or replace
  3. Recheck combustion readings and correct
  4. Look for sources of electrical noise such as a large motor starting at the same time
  5. Check the internal low water cutoff and any external limit between R and LIM

Models that show this code

13 models in Trinity Tft

Tft110Tft154Tft155Tft175Tft200Tft201Tft250Tft285Tft300Tft340Tft399Tft60Tft85

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting, Table 16-3. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.