NTI · Boiler
Lockout 112 Pilot test flame timeout
What the control is telling you
Pilot test flame timeout.
Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399
Models that show this code
13 models in Trinity Tft
Other codes on the same units
- Lockout 109 Ignition failed
- Lockout 11 Internal fault: Invalid Burner control state flag
- Lockout 11 Internal fault: Invalid Burner control state flag
- Lockout 112 Pilot test flame timeout
- Lockout 113 Flame circuit timeout
- Lockout 113 Flame circuit timeout
- Lockout 122 Light off rate proving failed
- Lockout 122 Light-off rate proving failed
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting, Table 16-3. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.