Hold / Lockout 81 Delta T limit
What the control is telling you
Temperature difference across the heat exchanger exceeded the delta-T limit, normally from too little water flow. Also the usual cause when the boiler bangs or hisses.
Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399
Likely causes
- Insufficient water flow
- Scale or magnetite on the heat exchanger
Test and repair steps
- Check fuse B
- Check the boiler pump
- Verify the piping matches the boiler piping section and system pressure is at least 15 PSI
- Clean scale from the heat exchanger with a descaler such as Fernox DS-40
Models that show this code
13 models in Trinity Tft
Other codes on the same units
- Hold / Lockout 67 ILK off - interlock string open
- Hold / Lockout 79 Outlet high limit
- Hold / Lockout 79 Outlet high limit
- Hold / Lockout 81 Delta T limit
- Hold / Lockout 85 Inlet/outlet inversion limit
- Hold / Lockout 85 Inlet/outlet inversion limit
- Hold / Lockout 88 Outlet temperature rise limit
- Hold / Lockout 88 Outlet temperature rise limit
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting, Table 16-3. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.