NTI · Boiler

Hold / Lockout 79 Outlet high limit

Critical severity Trinity Tft

What the control is telling you

Outlet water temperature reached the outlet high limit setting.

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

Likely causes

  • CH or DHW setpoint plus off hysteresis is above the high limit (factory limit 200 F / 93 C)
  • CH or DHW pump not working
  • Outlet high limit set too low
  • Outlet high limit response set to lock out

Test and repair steps

  1. Compare setpoint plus off hysteresis with the high limit and lower the setpoint if needed
  2. Check the CH and DHW pumps
  3. Raise the outlet high limit (maximum 200 F / 93 C)
  4. Set the outlet high limit response to recycle and hold unless local code forbids it, so the boiler does not lock out

Models that show this code

13 models in Trinity Tft

Tft110Tft154Tft155Tft175Tft200Tft201Tft250Tft285Tft300Tft340Tft399Tft60Tft85

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting, Table 16-3. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.