NTI · Boiler
Hold 95 Stack sensor fault
What the control is telling you
Control cannot read the flue gas temperature sensor.
Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399
Likely causes
- Sensor disconnected
- Faulty sensor
Test and repair steps
- Check the sensor plug at the bottom of the flue pipe inside the cabinet and the connection on the control board
- Measure the sensor resistance and compare to the thermistor chart
Models that show this code
13 models in Trinity Tft
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting, Table 16-3. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.