Hold 91 Inlet sensor fault

Medium severity Trinity Tft

What the control is telling you

Control cannot read the inlet water temperature sensor.

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

Likely causes

  • Sensor disconnected
  • Faulty sensor

Test and repair steps

  1. Check the sensor plug at the bottom of the heat exchanger and the connection on the control board
  2. Measure the sensor resistance and compare to the thermistor chart

Models that show this code

13 models in Trinity Tft

Tft110Tft154Tft155Tft175Tft200Tft201Tft250Tft285Tft300Tft340Tft399Tft60Tft85

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting, Table 16-3. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.