Navien · Heat pump
PC Low discharge superheat (liquid floodback risk)
What the control is telling you
Discharge temperature is only 5°C (9°F) or less above the coil temperature (T5 - T3).
Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)
Likely causes
- Overcharge
- Restriction or air in the lines
- T3 or T5 sensor reading wrong
- PCB fault
Test and repair steps
- Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
- Measure the T5 and T3 sensors against the 7.3 R-T Table, p.72. Replace a bad one.
- Restart the unit. Every minute, compare an infrared reading on the discharge line and coil with parameters 08 (T5) and 06 (T3), until it stops.
- Readings do not match the CHK display replace the outdoor PCB.
- Readings match and T5 minus T3 is not 5°C (9°F) or less: replace the outdoor PCB.
- T5 minus T3 really is 5°C (9°F) or less: liquid is getting back to the compressor. Look for overcharge, restriction or air in the lines.
Models that show this code
2 models in Navien NAZ
Other codes on the same units
- LC Compressor speed held back by condenser temperature
- LD Compressor speed held back by discharge temperature
- LE Compressor speed held back by drive module temperature
- LF Compressor speed held back by current
- PD High pressure too high in heating
- PRH Crankcase heater warm-up, no start yet
- dC Forced cooling
- df Defrost
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 4.2.18, p.52-53. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.