Navien · General

111 Over voltage at DC-Link

High severity WEC

What the control is telling you

The DC-link voltage on the power board is too high.

Applies to: WEC600

Test and repair steps

  1. Reset with Error Code Reset (ErSt) in Installer Setting Mode or unplug the power cord and plug it back in.
  2. If the code returns, call an authorized service professional and open the bypass valve to use feedwater until the error is cleared.

Other codes on the same units

  • 110 Power board overheat
  • 112 Over current at converter
  • 113 Over current at module
  • 114 Over current at module
  • 115 IGBT error
  • 116 Over voltage inverter
  • 117 Under voltage inverter
  • 118 Over frequency inverter

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien WEC service manual, p. 57. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.