Navien · General
051 Main CIP or TDS sensor relay
What the control is telling you
CIP process fault with the CIP dosing pump or outlet TDS sensor.
Applies to: WEC600
Likely causes
- CIP solution tank low
- Air in CIP line
Test and repair steps
- Check connection of CIP dosing pump and outlet TDS sensors.
- Check CIP solution level and refill if low.
- Purge air from the CIP line and reset.
- Clear with ErSt; if CIP fails again, call service.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien WEC service manual, p. 53. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.