Navien · Combi boiler

Outdoor temperature Outdoor temperature display

Normal status Navien NCB-H

What the display is showing

Digits showing the outdoor temperature (sensor needed).

Applies to: NCB-190/060H to NCB-250/150H

Settings for these units

Minimum installation clearances (indoor) · Navien NCB-H

SideMinimum
Top9 in (229 mm)
Back0.5 in (13 mm)
Front4 in (100 mm)
Sides3 in (76 mm)
Bottom12 in (300 mm)

Indoor wall-hung only; ambient must stay above 32°F (0°C).

Do not install on carpet; leave room for service.

Water quality limits (DHW and system fill) · Navien NCB-H

ContaminantMax allowed
Total hardness200 mg/l (12 grains/gallon)
Aluminum0.05 to 0.2 mg/l
Chloride250 mg/l
Copper1.0 mg/l
Iron0.3 mg/l
Manganese0.05 mg/l
pH6.5 to 8.5
Sulfate250 mg/l (DHW table); 205 mg/l (fill table)
Total dissolved solids500 mg/l
Zinc5 mg/l
Chlorine (fill water)4 mg/l

Scale damage from poor water is not covered by warranty.

Manual shows sulfate 250 mg/l on p.23 and 205 mg/l on p.29 - check local guidance.

Models that show this code

5 models in Navien NCB-H

NCB-190/060HNCB-190/080HNCB-240/110HNCB-240/130HNCB-250/150H

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NCB-H User's Information Manual (V1.0 Apr 2024), 2.3.1 Icons and Digital Display, p.8. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.