Navien · Boiler

E060 Dual venturi fault

Medium severity Navien NHB-HNavien NFB-H

What the control is telling you

The dual venturi did not respond correctly. Manual action: check the dual venturi.

Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers

Likely causes

  • Dual venturi actuator stuck or failed
  • Loose wiring to the dual venturi
  • PCB output problem

Test and repair steps

  1. Run Test Mode > 9. Dual Venturi and confirm it switches on and off.
  2. Check Dual Venturi Status in the Input/Output Status menu.
  3. Warning: Power off, then check the dual venturi connector and wiring.
  4. Replace the dual venturi if it does not operate when the output is on.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.